We provide water treatment and prevention of Legionnaires Disease in Cooling Towers, Chill Water, and Hot Water Systems. Our goal is to help you be compliant with NYC Cooling Tower Regulations in prevention of Legionnaires Disease.
You are required by law to do:
Routine inspections and Legionella Testing of active cooling towers by a qualified professional prior to seasonal start-up and every 90 days!
Respond appropriately to an elevated Legionella culture sampling result exceeding 1,000 colony-forming units (CFU) per milliliter (mL) and you notify the local health department within 24 hours!
Twice a year your cooling tower be disinfected by a licensed pesticide applicator or technician certified by NY State!
A maintenance plan for each cooling tower be developed and strictly followed!
Each year by NOVEMBER 1st certification be obtained from a credentialed inspector stating a maintenance plan for each cooling tower has been followed and all cooling tower regulation requirements have been met!
We can help to assist you with these demands by providing:
3 times per week Water Testing of the Cooling Tower
Weekly Inspection of the Cooling Tower
Weekly Inspection of the Chemical Station
Weekly Dip-slide Testing of the Cooling Tower
Communicating with the Water Treatment Vendor and all other Necessary Parties when things are out of range.
Emergency Disinfections of Cooling Towers or Domestic Water Systems.
Development of a Compliant Cooling Tower Maintenance Program and Plan